More than 700 lift backup units installed in Hyderabad, and a growing book across Pune. This is the part of a building where a power cut stops being an inconvenience and becomes a rescue call.

Book a site survey

Request a quote

About Elevators & Building Services. We reply within one working day.

e.g. 12 kW IT load, or 60 kVA three phase

Equipment on the circuit, backup time needed, site location, and any deadline.

+91 86686 14124
Elevators & Building Services — power systems supplied by Extreme Power System, Pune

What actually goes wrong

A DG takes eight to fifteen seconds to start and load, assuming it starts. In that window the car is stationary between floors with people in it, and if the DG fails to start the wait becomes an hour and a phone call to the fire brigade. A lift inverter is independent of both the DG and the incoming supply, and it acts in under a minute. Lifts are the sector we have installed in most — more than 700 units across housing societies, commercial buildings and hospitals — so the controller interfaces are territory we already know.

Working in elevators & building services

Specification stage

What to get right

The decisions on this list are the ones that are expensive to change after the equipment is on site.

  • Regenerative load

    A descending loaded car feeds power back into the drive. A lift inverter absorbs it; a general-purpose one trips or is damaged.

  • Controller compatibility

    VVVF controller interfaces differ between makes. There is no universal wiring — the machine room gets surveyed before quoting.

  • Machine room temperature

    Terrace machine rooms in Pune run above 40 °C in summer, which can halve battery life. Annual load testing is not optional.

  • Direction of least load

    The car should travel the direction that requires least energy. Correct commissioning is what makes the rescue reliable at low state of charge.

  • Building-wide services

    Fire panels, emergency lighting and access control also need holdover. They are usually forgotten until the handover inspection.

  • Statutory position

    Lift rules are state-administered. Check the current Maharashtra rules and your lift inspector for what applies — a lift inverter is standard specification on new commercial work regardless.

Typically specified

What we supply into this sector

Elevators & Building Services

Questions we get asked

Anything not covered here, call us — most of it is faster to answer on the phone.

01Can a lift inverter be retrofitted to an existing lift?

In most cases yes. We need the machine rating, the drive type and the controller make, and the machine room gets surveyed first because the interface differs between VVVF controllers. Retrofitting does not normally require replacing the drive.

02How long does the lift keep running on backup?

It does not need to — the lift keeps running. A backup system carries normal service at normal speed for up to eight hours, so the car in transit completes its journey and the next passenger never knows the mains failed. A controlled landing only happens at the end, if the bank runs down before the supply returns.

03Is an automatic rescue device mandatory in India?

Treat it as required and confirm locally. ARDs are named as a required safety feature across the Indian lift codes and most state Lift Acts, and enforcement in Maharashtra has tightened. The code position also moved recently: IS 17900, based on EN 81-20/50, superseded IS 14665, IS 15785 and IS 14671 for new installations from 22 December 2025, while adoption into individual state Lift Acts is happening state by state. Older lifts remain certified to the code they were installed under. Confirm the current position for your building with your lift contractor and the state Electrical Inspectorate before ordering — we build to the specification you are given.

04What is the difference between a lift ARD and a lift inverter?

Scope. An ARD is a rescue device: on mains failure it moves the car to the nearest floor, opens the doors and stops. A lift inverter keeps the lift in normal service — full speed, full travel, calls answered — for as long as the battery lasts. An ARD prevents entrapment; an inverter prevents interruption. A residential building with a generator usually needs the first. A hospital, hotel or a building with no DG usually wants the second.

05Will an ARD or lift inverter work with our VVVF controller?

Generally yes, but the interface is the thing to check, not the rating. VVVF drives differ in how they signal a supply failure and how they expect the rescue sequence to be initiated, and some regenerate into the supply on descent. We ask for the controller make and model, the drive type and the machine rating before quoting, and survey the machine room on anything we have not interfaced with before.

06Does a lift on a DG set still need backup?

Usually, because of the gap. A generator takes time to start, accept load and stabilise, and during that window the car is stationary between floors with passengers in it. An ARD or inverter covers the changeover, and it also covers the case every building eventually meets — the DG that does not start. Sizing also matters here: lift starting current is well above running current, and a lift is one of the loads most likely to be underestimated on a DG.

We will do the load grading with you

Site survey, load list and a single-line diagram before anything is quoted. That is where the specification is actually decided.