10 kVA online UPS

10 kVA

The crossover point in the range. Eight kilowatts of real output, and the only rating we build with either input configuration — single phase on a 192 V bank, or three phase on a 240 V bank. Output is single phase in both cases.

Get a quote

Request a quote

About 10 kVA Online UPS. We reply within one working day.

e.g. 12 kW IT load, or 60 kVA three phase

Equipment on the circuit, backup time needed, site location, and any deadline.

Full Online UPS range
10 kVA
Rated capacity
8.0 kW
Real output at 0.8 pf
192 V (1Ph input) or 240 V (3Ph input)
Battery bus
1 phase
Input supply

10 kVA Online UPS — rating card

10 kVA Online UPS — rating card
SeriesEPS-1PH-SERIES
Rated capacity10 kVA
Rated output power8.0 kW
Input configurationSingle phase + neutral, 220 / 230 / 240 VAC
Input voltage range170 V – 280 V
Output configurationSingle phase + neutral + ground
Rated output voltage220 / 230 / 240 VAC ±1%
Battery voltage192 V (1Ph input) or 240 V (3Ph input)
TopologyTrue double conversion online
Transfer time0 ms (true online)
EfficiencyUp to 96%
Output waveformPure sine wave
THDv (linear load)< 3%
THDv (non-linear load)< 5%
Output power factor0.8 lag
Voltage regulation±1%
Overload capacity110–150%: 30 s · > 150%: 2 ms
Input frequency48 – 52 Hz
Input power factor> 0.90 (PFC)
Output frequency50 Hz
Battery typeExternal tubular and SMF
Charge currentAdjustable 1 A – 12 A
Recharge time< 8 hrs to 90% capacity
Battery protectionOver-voltage / under-voltage
Operating temperature0 °C – 40 °C
Humidity5% – 95%, non-condensing
CommunicationRS-232
Protection classIP20
CoolingForced air, variable speed fans
MobilityHeavy-duty caster wheels

Typical values for the standard build. Configured to order — your general arrangement drawing carries the figures that apply.

10 kVA Online UPS — questions

Anything not covered here, call us — most of it is faster to answer on the phone.

Should I take the single-phase or three-phase input version of the 10 kVA?

If you have a three-phase connection, take the three-phase input. Eight kilowatts drawn from one phase is a heavy single-phase load and it unbalances the incoming supply; spread across three phases it is unremarkable. Output is single phase on the EPS-3PH1PH-SERIES and three phase on the EPS-3PH3PH-SERIES, both available at this rating.

Does the 10 kVA give a three-phase output?

It depends on the series. The EPS-3PH3PH-SERIES outputs three phase plus neutral plus ground from 10 kVA up. The EPS-1PH and EPS-3PH1PH series output single phase plus neutral plus ground — on the latter, the three-phase reference is to the input side only. At 10 kVA both are available, so say which the load needs and we will quote the right one.

Other capacities

Coverage

Where we supply and attend

10 kVA Online UPS units are built at our Pune works and delivered, installed and commissioned across the city and the industrial belt around it.

Outside these areas we contract individually against distance, and we will tell you honestly if the response time you need is not one we can hold to. All areas served

Not sure this is the right size?

Send the load list. Sizing against inrush rather than running load is where most undersized installations go wrong, and it costs nothing to check.

Get a quote

Request a quote

About 10 kVA Online UPS. We reply within one working day.

e.g. 12 kW IT load, or 60 kVA three phase

Equipment on the circuit, backup time needed, site location, and any deadline.