20 kVA online UPS
20 kVA
Sixteen kilowatts of single-phase output from a three-phase input, on either a 240 V or a 360 V bank. A common rating for imaging suites, mid-size server rooms and production control infrastructure.
- 20 kVA
- Rated capacity
- 16.0 kW
- Real output at 0.8 pf
- 240 V or 360 V
- Battery bus
- 3 phase
- Input supply
20 kVA Online UPS — rating card
| Series | EPS-3PH1PH-SERIES (1φ out) · EPS-3PH3PH-SERIES (3φ out) |
|---|---|
| Output options | Single phase, or three phase + neutral |
| Rated capacity | 20 kVA |
| Rated output power | 16.0 kW |
| Input configuration | 3 phase + neutral, 380 / 400 / 415 VAC |
| Input voltage range | 330 V – 480 V |
| Output configuration | Single phase + neutral + ground |
| Rated output voltage | 220 / 230 / 240 VAC ±1% |
| Battery voltage | 240 V or 360 V |
| Topology | True double conversion online |
| Transfer time | 0 ms (true online) |
| Efficiency | Up to 96% |
| Output waveform | Pure sine wave |
| THDv (linear load) | < 3% |
| THDv (non-linear load) | < 5% |
| Output power factor | 0.8 lag |
| Voltage regulation | ±1% |
| Overload capacity | 110–150%: 30 s · > 150%: 2 ms |
| Input frequency | 48 – 52 Hz |
| Input power factor | > 0.90 (PFC) |
| Output frequency | 50 Hz |
| Battery type | External tubular and SMF |
| Charge current | Adjustable 1 A – 12 A |
| Recharge time | < 8 hrs to 90% capacity |
| Battery protection | Over-voltage / under-voltage |
| Operating temperature | 0 °C – 40 °C |
| Humidity | 5% – 95%, non-condensing |
| Communication | RS-232 |
| Protection class | IP20 |
| Cooling | Forced air, variable speed fans |
| Mobility | Heavy-duty caster wheels |
Typical values for the standard build. Configured to order — your general arrangement drawing carries the figures that apply.
20 kVA Online UPS — questions
Anything not covered here, call us — most of it is faster to answer on the phone.
What incoming supply does a 20 kVA UPS need?
A three-phase connection at 380 to 415 V. The input tolerates 330 V to 480 V, which is a wide enough window for most Pune industrial feeders without a stabilizer in front. Cable and breaker sizing goes on the general arrangement drawing we issue with the quotation.
Other capacities
3 kVA Online UPS
5 kVA5 kVA Online UPS
6 kVA6 kVA Online UPS
7.5 kVA7.5 kVA Online UPS
10 kVA10 kVA Online UPS
15 kVA15 kVA Online UPS
30 kVA30 kVA Online UPS
40 kVA40 kVA Online UPS
50 kVA50 kVA Online UPS
60 kVA60 kVA Online UPS
80 kVA80 kVA Online UPS
100 kVA100 kVA Online UPS
120 kVA120 kVA Online UPS
150 kVA150 kVA Online UPS
180 kVA180 kVA Online UPS
200 kVA200 kVA Online UPS
Where we supply and attend
20 kVA Online UPS units are built at our Pune works and delivered, installed and commissioned across the city and the industrial belt around it.
Outside these areas we contract individually against distance, and we will tell you honestly if the response time you need is not one we can hold to. All areas served
Not sure this is the right size?
Send the load list. Sizing against inrush rather than running load is where most undersized installations go wrong, and it costs nothing to check.