15 kVA online UPS

15 kVA

Twelve kilowatts of single-phase output taken from a balanced three-phase input. Offered on a 240 V bank (twenty batteries) or a 360 V bank (thirty), which is the decision that sets your runtime ceiling.

Get a quote

Request a quote

About 15 kVA Online UPS. We reply within one working day.

e.g. 12 kW IT load, or 60 kVA three phase

Equipment on the circuit, backup time needed, site location, and any deadline.

Full Online UPS range
15 kVA
Rated capacity
12.0 kW
Real output at 0.8 pf
240 V or 360 V
Battery bus
3 phase
Input supply

15 kVA Online UPS — rating card

15 kVA Online UPS — rating card
SeriesEPS-3PH1PH-SERIES (1φ out) · EPS-3PH3PH-SERIES (3φ out)
Output optionsSingle phase, or three phase + neutral
Rated capacity15 kVA
Rated output power12.0 kW
Input configuration3 phase + neutral, 380 / 400 / 415 VAC
Input voltage range330 V – 480 V
Output configurationSingle phase + neutral + ground
Rated output voltage220 / 230 / 240 VAC ±1%
Battery voltage240 V or 360 V
TopologyTrue double conversion online
Transfer time0 ms (true online)
EfficiencyUp to 96%
Output waveformPure sine wave
THDv (linear load)< 3%
THDv (non-linear load)< 5%
Output power factor0.8 lag
Voltage regulation±1%
Overload capacity110–150%: 30 s · > 150%: 2 ms
Input frequency48 – 52 Hz
Input power factor> 0.90 (PFC)
Output frequency50 Hz
Battery typeExternal tubular and SMF
Charge currentAdjustable 1 A – 12 A
Recharge time< 8 hrs to 90% capacity
Battery protectionOver-voltage / under-voltage
Operating temperature0 °C – 40 °C
Humidity5% – 95%, non-condensing
CommunicationRS-232
Protection classIP20
CoolingForced air, variable speed fans
MobilityHeavy-duty caster wheels

Typical values for the standard build. Configured to order — your general arrangement drawing carries the figures that apply.

15 kVA Online UPS — questions

Anything not covered here, call us — most of it is faster to answer on the phone.

Why does a 15 kVA UPS have a three-phase input but a single-phase output?

Because the load is single phase but the draw is too large to take from one phase of the incoming supply. Rectifying from all three phases balances the load on your connection and keeps the incoming cable and protection sensibly sized, while the inverter still produces the single-phase supply your equipment expects.

240 V or 360 V battery bank on the 15 kVA?

The 360 V bank stores considerably more energy for the same amp-hour cell, so it is the choice where backup time matters. The 240 V bank is twenty cells against thirty, so it costs less and takes less floor space. Tell us the runtime you need and the answer follows from it.

Other capacities

Coverage

Where we supply and attend

15 kVA Online UPS units are built at our Pune works and delivered, installed and commissioned across the city and the industrial belt around it.

Outside these areas we contract individually against distance, and we will tell you honestly if the response time you need is not one we can hold to. All areas served

Not sure this is the right size?

Send the load list. Sizing against inrush rather than running load is where most undersized installations go wrong, and it costs nothing to check.